Two-stage compressor system.
Features of the C1H High-Temperature Heat Pump.
High Water Temperature 90℃
The advantage of the R134a system is its ability to produce high water temperatures (greater than 80℃ ), but the drawback is its unsuitability for use in low-temperature environments. When the ambient temperature drops below 0℃, the system's efficiency is significantly reduced. The R32 inverter system is suitable for low-temperature environments (below minus 20℃), but the maximum water output temperature of the R32 system is limited to 70℃. Therefore, combining the two systems by exchanging heat between the condensing side of the R32 system and the evaporating side of the R134A system through a heat exchanger can leverage the advantages of each system. This allows the heat pump to operate in low-temperature environments while also generating high water temperatures.
The condenser of the R32 system functions as the evaporator for the R134a system, consistently providing a source temperature above 0°C. This ensures an efficient energy supply for the R134a compressor, enabling it to produce high water temperatures.
Line-Up
Model | C1H Pro-12 | C1H Pro-15 | C1H Pro-19 | C1H Pro-26 | C1H Pro-38 | C1H Pro-53 | C1H Pro-100 | ||
Performance at air 7°C, water 35°C. | heating capacity | kW | 12.0 | 15.0 | 19.5 | 26.4 | 38.7 | 54.0 | 105.0 |
Input power | kW | 2.6 | 3.2 | 4.2 | 5.7 | 8.4 | 11.8 | 22.9 | |
COP | W/W | 4.65 | 4.65 | 4.60 | 4.61 | 4.59 | 4.58 | 4.58 | |
Performance at air 7°C, water 75°C. | heating capacity | kW | 10.9 | 13.7 | 17.7 | 24.0 | 35.2 | 49.1 | 95.6 |
Input power | kW | 3.4 | 4.3 | 5.7 | 7.7 | 11.5 | 16.0 | 31.3 | |
COP | W/W | 3.20 | 3.21 | 3.11 | 3.12 | 3.05 | 3.07 | 3.05 | |
Performance at air -12°C, water 75°C. | heating capacity | kW | 9.2 | 11.5 | 14.9 | 20.2 | 29.6 | 41.3 | 80.3 |
Input power | kW | 3.4 | 4.2 | 5.7 | 8.1 | 11.8 | 16.2 | 32.2 | |
COP | W/W | 2.70 | 2.71 | 2.60 | 2.50 | 2.50 | 2.55 | 2.49 | |
Power supply type | P/V/Hz | 1/230/50 | 3/380-415/50 | ||||||
Number of required photovoltaic panels | 580W/PCS | 8 | 9 | 13 | 18 | 27 | 36 | 72 | |
Maximum outlet water temperature | ℃ | 90 | |||||||
Working ambient temp range | ℃ | -25~43 | |||||||
Compressor (R290+R134A) | Type | / | R32 Hybrid inverter&EVI compressor +R134A On/Off Compressor | ||||||
Fan | Fan type | / | High efficiency axial flow fan | ||||||
Motor type | / | DC | |||||||
Evaporator | First evaporator | Type | Solar panel heat exchanger | ||||||
Second evaporator | Type | Finned heat exchanger | |||||||
Condenser | First condenser | Type | High-efficiency tank heat exchanger / coaxial casing heat exchanger | ||||||
Second condenser | Type | Plate heat exchanger | |||||||
Needed water flow | User side | m³/h | 2.06 | 2.58 | 3.27 | 4.47 | 6.54 | 9.12 | 17.20 |
Size | Cabinet | mm | 1080x420x 1392 | 1080x420x 1392 | 780×780× 975 | 780×780× 1075 | 1450×750 ×1400 | 1500×800 ×1550 | 2120×110 0×2140 |
Weight | rough weight | kg | 125 | 144 | 150 | 175 | 320 | 450 | 720 |
Noise level | dB(A) | 54 | 58 | 62 | 62 | 68 | 68 | 71 |